CBTO Optimized

CBTO Optimized

Description

The aim of the CBTO ECOLAN LV Switchboard is to spread the LV supply from the distribution transformer into several independent feeders by means of fuse switches BTVC TRIVER+.

The main parts are: 3P+N vertical disconnector with upper incoming connection, an additional power supply (for emergency purposes), an insulating panel, fuse switches (BTVC TRIVER+) and auxiliary circuits (measurement, substation services, etc.). In case of floor fixing it comprises a metallic frame. The incoming connection is designed for 4 cables of 240 mm2 per phase and 3 cables of 240 mmfor the neutral.

References

References

General Specifications
Rated voltage 440V
Rated current 1000 / 1600 A
Connection of power generator rated current 1000 / 1600 A
Operation Seccionador 3F+N Maniobra unipolar
Number of outgoings 04/05/2008
Type of outgoings BTVC TRIVER+
Standard UNE-EN 61439-1
UNE-EN 61439-5
Rated insulation voltage Phase-Ground * 10 kV
Rated insulation voltage Phase-Phase 2,5 kV
Rated impulse withstand voltage Phase-Ground* 20 kV
Rated short-time withstand current 15 / 25 kA
Rated peak withstand current 31,5 / 52,5 kA
Self-extinguishing materials UNE EN 60 695-11-10
UNE EN 60 085
Protection degree IP2X UNE-EN 20324
IK08 UNE-EN 50102
* We consider ground, a metallic sheet covering the front if the switchboard connected to the switchboard metallic parts.