PRODUCTOS

Archives

CBTO-AL4

Specifications of the AL4:

Incoming Lateral
Rated current 1000 A
Installation Indoor
Enclosure Metallic frame
Operations 3P+N Single pole disconnector
Outgoing types BTVC TRIVER+*
No. of outgoings 4
Options Auxiliary circuits
No. of incoming cables
2 x 240 mm2
Weight 75 kg

 

* Three pole vertical fuse switch TRIVER+.
No. of outgoings changes when combinating the range of fuse switches
TRIVER+ NH-00/1/2/3.

 

más información

CBTI-T-IP

Telemanagement Outdoor Substation LV Switchboard with incoming directly to the load break switch (CBTI-T-IP) has through the right side of the middle enclosure and outgoing through the bottom of the lower enclosure.

Three different partitions:

– Upper enclosure for the Telemanagement equipments.
– Middle enclosure for the load break switch.
– Lower enclosure for the substation outgoings.

Specifications of the CBTI-T-IP:

Incoming 
Lateral incoming directly to
the load break switch
Rated current 400 A
Installation  Outdoor pole mounted
Enclosure  PNT Polyester 2 doors
Operation Load break
Outgoing types  BTVC TRIVER+*
No. of outgoings 3
Options Mounting frame
No. of incoming cables 1 x 240 mm2
Weight 50 kg

* Three pole vertical fuse switch TRIVER+.
No. of outgoings changes when combinating the range of fuse switches
TRIVER+ NH-00/1/2/3.

más información

CBTO-AS8

CBT0-AS8

The aim of the CBTO ECOLAN LV Switchboard is to spread the LV supply from the distribution transformer into several independent feeders by means of fuse switches BTVC TRIVER+.

The main parts are: 3P+N vertical disconnector with upper incoming connection, an additional power supply (for emergency purposes), an insulating panel, fuse switches (BTVC TRIVER+) and auxiliary circuits (measurement, substation services, etc.). In case of floor fixing it comprises a metallic frame. The incoming connection is designed for 4 cables of 240 mm2 per phase and 3 cables of 240 mmfor the neutral.

 

No. of outgoings changes when combinating the range of fuse switches TRIVER+ NH-00/1/2/3.

BTVC – TRIVER+ is the brand of our range of Vertical three-pole fuse switches that can be disconnected on Load.

 

más información

NH 1/2 | 250/400 A

1 Pole horizontal design protected fuse bases

    • NH 1 and Nh2 size.
    • Rated current up to 400 A.
    • Rated voltage  up to 690 V.
    • Open fuses bases or protected fuses bases design.

 

más información

NH 00 | 160 A | 185 mm

IP20 protected busbar system supports three pole vertical design fuse switches size NH 00 up to 160 A. The result is a complete IP20 protected system, that fulfills requirements according to IEC 60529.

  • Three pole vertical design fuse switches.
  • NH00 size fuses.
  • Distance between busbars 185 mm.
  • Rated operational current up to 160 A.
más información