SIBA fuses | 800 V AC

The new series of SIBA NH fuses with operating class: gRL (gS) has been developed for the line protection of the new String Inverters.

Due to the use of special geometries of melting elements, in comparison to the conventional line protection fuses of operating class: gG, a considerably faster operation at short circuits and thus optimum protection of the inverters has been realized. In the space-saving NH standard designs, the fuse links achieve a maximum breaking capacity of 120 kA with a test voltage of 800 V.

The power losses of series NH 00, NH 1 and NH 3 have been designed for the respective maximum power acceptance
of the corresponding NH fuse bases and fuse switches.

Operation class gG

NH size Rated
Current (A)
Power loss (W) Reference
000 6 2 2030813
000 10 2,5 2030813
000 16 4 2030813
00 20 2,5 2030913
00 25 3,0 2030913
00 32 4,0 2030913
00 40 4,5 2030913
00 50 5,0 2030913
00 63 6,5 2030913
01 50 5,0 2031113
01 63 6,5 2031113
01 80 7,5 2031113
01 100 9,0 2031113
01 125 10 2031113
01 160 13 2031113
03 160 13 2031313
03 200 18 2031313
03 250 20 2031313
03 315 28 2031313

Operation class gRL (gS)

NH size Rated
Current (A)
Power loss (W) Reference
00 32 5 2030934
00 35 6 2030934
00 40 7 2030934
00 50 8 2030934
00 63 10 2030934
00 80 11 2030934
00 100 12 2030934
00 125 13 2030934
01 80 13 2031134
01 100 15 2031134
01 125 18,0 2031134
01 160 19 2031134
01 180 20 2031134
01 200 21 2031134
03 200 2031334
03 250 26 2031334
03 315 31 2031334
03 350 35 2031334
03 400 41 2031334
03 450 43 2031334
03 500 47 2031334

 