Low voltage panels for electric vehicle charging stations

DESCRIPTION

Panel intended for the protection of low-voltage lines in indoor transformer substations that supply the different charging points through converters/rectifiers in fast and ultra-fast charging infrastructures for electric vehicles equipped with medium and high power chargers.

  • based on vertical design fuse-switchgear technology
  • greater safety and performance
  • protection against overloads, short circuits and overvoltages

It has a high capacity and resistance, with a rated current of 2000 A and upwards and up to 8 feeders, which makes it suitable for high energy demand applications. Therefore, it is able to withstand current peaks at the feeders without compromising its lifetime, ensuring reliable and long-lasting performance.

 

MAXIMUM RELIABILITY

TRIVER vertical fuse switches provide a highly efficient alternative to circuit breakers on distribution panel feeder lines. They act as switches, enabling the line to be controlled while under load. They are available in 3-pole and single-pole phase by phase versions.

 

MONITORING

The panels can be supplied with our low-voltage distribution network monitoring and remote supervision systems.

 

EXPANDABLE

Charging stations are still in their early days, so the scenario may change. One great advantage of our panels is that they can be expanded, so additional posts can be installed with no problems.
The roll-out of charging stations has only just begun and demand is expected to increase in the coming years, so our panels are made to be expandable. If more charge points and therefore more feeder lines are needed in the future, an extension switchboard can be added.

 

MORE COMPACT

The great advantage of fuse holders is that they take up very little space, which makes for a compact, tidy low-voltage panel design.
These distribution panels also use less space that conventional panels with circuit breakers. This means that the transformer substations installed are also more compact.

 

LOWER COSTS

The smaller size of these installation means that costs are lower. With the extension switchboards that we offer as part of the range, service capacity can be increased without enlarging the installation.
On the other hand, it should be noted that the use of three-pole fuse switches as protection and distribution elements is more economical than the massive use of circuit breakers per feeder.

Technical data

GENERAL PROTECTION LV PANEL - MULTIPLE FEEDER

Technical data
Current 2000 A / 2500 A / 3200 A*
General manoeuvre 3P + N main circuit breaker
Incoming Triver 3-pole vertical fuse switch + NH 00/1/2/3
Type of feeders BTVC Triver + NH 00/1/2/3
Nº of feeders 4/8/12/… with NH 1/2/3 *
Options Expandable
Monitoring/advanced supervision
Auxiliary circuits
Differential protection
Measuring
Surge protection
Installation Inside transformer substation (Metal enclosure )
Dimensions 2131 x 950 x 503 mm

GENERAL PROTECTION LV PANEL - 1 FEEDER

Technical data
Current 630 A / 800 A / 1000 A / 1250 A / 1600 A*
General manoeuvre 3P + N main circuit breaker
Incoming Top mounting: 4 cable 240 mm2 per fase
Type of feeders Direct form the circuit breaker
Nº of feeders 1 feeder direct form the circuit breaker
Options Auxiliary circuits
Differential protection
Surge protection
Interlocking of the switch by a lock
Installation Inside transformer substation (Metal enclosure)
Nº. of cables for the incoming For 630 y 800 A: 2  x 240 mm2
For 1000 A: 3 x 240 mm2
For 1250 y 1600 A: 4 x 240 mm2
Dimensions 1446 x 580 x 290 mm

AUXILIARY SERVICES CABINET

Components
Single-phase or three-phase transformer
Magnetotermic circuit breakers
Current circuit breakers
Plug base
Dimensions 766 x 500 x 297 mm

 