CBTI

CBTI Outdoor Substation’s LV Switchboard

Description

Outdoor substation LV Switchboard (pole mounted type) according to standard NI 504404. Feeders by means of fuse switches NH 00 BTVC TRIVER+ (160 A). Maximum cross-section for the outgoing cable 95 mm2. Incoming and outgoing connections through the bottom of the enclosure.

Specifications of the CBTI:

Incoming
Through the bottom part of the
switchboard directly to the busbar
Rated current 630A
Installation Outdoor
Enclosure PNT Polyester
Operation
Outgoing types BTVC TRIVER+*
No. of outgoings 3
Options Auxiliary circuit
No. of incoming cables 2 x 240 mm2
Weight 22 kg
* Three pole vertical fuse switch TRIVER+.
No. of outgoings changes when combinating the range of fuse switches
TRIVER+ NH-00/1/2/3.

 

Contact with us